1) Soil resistivity
2) Tolerable limits of body current
Currents higher than 60 mA may lead to ventricular fibrillation, injury & death.
3) Fault current
As the earthing system has to carry the earth currents, the maximum earth fault current likely to flow in the system is considered for designing of earthing. A good earthing system for substation can be designed using an earth mat which is formed by a grid of horizontally buried conductors which serves to dissipate the earth fault currents to earth, also as an equipotential bonding conductor system, along with required number of vertical earth electrodes which are connected to the points of earthing of various equipments, structures and also interconnected with the horizontal earth mat. M.S. rods are generally used for the earthing of substation.
Total Earth resistance of the station system must be below 3 ohms for low voltage domestic system, below 0.5 ohms for low voltage and medium voltage sub- station, and below 0.1 ohm for 220 KV and 400 KV sub-station and power plants. If value of Earth Pit resistance is found high, then it is to be treated to bring back the value within the normal range.
0 Comments